UPS报警详解

在使用UPS时会出现不同的报警,现将报警出现时的意义及处理方法进行说明如下:

A01 :     MAINS FAULT CYCLE DETECTION ERROR(相序错)

POSTIL :  The R1 phase rotation is wrong.

注释:    输入电源相序错误,更换任二相输入接点即可

A02 :     MAINS FAULT BATTERY IS DISCHARGING(主电源故障)

POSTIL :  The R1 voltage is absent or out of tolerance.

注释:    输入电源断电或超出允许范围,检查UPS 上游之输入开关是否跳脱,或于UPS 操作面板上检查输入电压值是否异常;同时检查UPS的后备电池组是否处于放电状态

A03 :     AUXILIARY MAINS FAULT(旁路电源故障)

POSTIL:  The auxiliary input mains voltage is absent, out of tolerance

注释:  输入电压断电、超出规范或相序错误;报警出现的同时如果有A02报警同时存在时表示外电网有问题,电池组正在放电。正常报警,检查外电网。

A04 :OVERLOAD IMMINENT SHUTDOWN(过载机器即将关机)

POSTIL: The power required by the load exceeds the power available via the UPS.

ATTENTION : after the maximum overload time, the load is no longer powered.

注释:   负载量大于UPS 之额定容量请确认各相负载量不要大于UPS 各相之额定容量可于屏幕上检查各相之负载量并移除多余之负载。

注意:本UPS 具有过载承受能力,(过载能力(T°<30°C) 125%负载时,承受时间为10分钟,150%过载时,承受时间为1分钟)当过载承受时间届满时,UPS 将停止供电。

A05 :     UPS FAULT(UPS故障)

POSTIL: This is the UPS general alarm. This alarm is activated when at least one alarm is present.

注释:   此为UPS 之综合性警报,任何一个UPS 内部警报都会导致本警报之产生;当此报警出现时,伴随有8位16进制代码,可具体查找到报警的信息。可通过报警复位对其进行恢复。

A06 :     BATTERY FAULT(电池故障)

POSTIL :  The battery voltage is out of tolerance. .

注释:   电池电压超出范围。检查电阿池组电压,是否低于最低允许值(单只电池最低放电电压为10.5V),如果电压低限,要及时恢复主电源供电,或将UPS负载减小。此报警一般是长时间放电引起或是由于电池组中电池有问题。

A07 :     BATTERY CIRCUIT OPEN FAULT(电池开路报警)

POSTIL: Batteries are not connected. The battery switch or breaker is open or the battery fuses are broken.

注释:   电池开关F1尚未投入,或电池组保险烧断。请检查电池开关及保险

 

A08 :     MANUAL BY-PASS ACTIVE(手动旁路激活)

POSTIL: a)For UPS 10 to 30 kVA, the output switch Q2 is in position 2.

b)For UPS 40 and 60 kVa, the switch Q5 is closed.

注释:   a)10 – 30 KVA UPS输出开关Q2 置于2 段位置。

         b)40 – 60 KVA UPS手动旁路开关Q5 已投入。

此一情况代表负载直接由市电供电,在UPS开机或关机及转旁路维修时会出现此报警。请不要随意闭合手动开关

A09 :     MIMIC PANEL FAULT(仿真流程控制面板故障)

POSTIL: The mimic panel is defective. The information displayed may be wrong. It may be a problem with mimic panel pcb, DE pcb or the CAN BUS cable.

注释:   仿真流程控制面板故障,此时显示出来的数值可能已经错误,本故障原因于PCB DE 板与仿真流程控制面板无法通讯,仿真流程控制面板、PCB DE 板故障及通讯连接线故障都可能引起此一警讯。出现此报警,机器正常工作

A10 PRESERVING(预留报警,未使用)

A11 :     ACTIVE FILTER ALARM(有缘滤波器故障)

POSTIL: This alarm may be only displayed on DIGYS Å. In this case a specific alarm code in hexadecimal is displayed (like service code), UPS is still running but the active filtre is off.

注释:  如果整流器之输入电流谐波超过5% 即出现本警讯,此时UPS 仍然可正常工作;正常报警,当输入谐波降低后,报警消失。

A12 :     OPT2 BOARD ALARM(外部接口板故障)

POSTIL:  This alarm is activated when at least one of the inputs of the dry contact pcb (S6.839.x/04) is closed.

注释:  外部接口板(选购)故障。检查标号为6839X04的PCB板

 

 

 

 

 

 

 

 

 

A13 :   INVERTER MAINS SYNCHRONIZATION FAULT(主从不同步报警)

POSTIL :  Inverter and mains are not synchronized. If the alarm A03 is also active, it means that the non synchronization is due to R2 frequency out of tolerance.

If it’s the only active alarm, it means that R2 frequency is subject to continuous variations. This is typical when the UPS is supplied by an emergency generator.

注释:  逆变器与市电不同步,如果同时出现A03 之警报,则表示本警报是因为旁路电源之电压或频率异常而引起的,通常当UPS 由发电机供电时较容易出现这种状况。当市电的电压或频率恢复时,报警解除,正常报警,不需要认为动作。

 

A14 :  VENTILATION FAN FAULT(风机故障)

POSTIL: The UPS internal temperature is too high. The possible reasons are :

-          One or more fans are broken.

-          The room temperature is more than 40°C.

-          There is not enough space around the UPS cabinet.

注释:  UPS 内部温度过高。此报警可能由于下列原因:

        一个或多个风机故障 

        环境温度超过40°C

  UPS 摆设位置未依照规范致使散热空间不足

A15 :     BATTERY TEST ALARM(电池测试报警)

POSTIL: The result of the battery test is not good.

注释:   UPS 将每隔一段时间执行电池放电测试以检查电池是否正常,本警报之出现代表电池放电测试时电池放电能力不足,需要及时更新。出现此报警需检查电池组是否还可继续使用。

A18:   PERIODIC SERVICE CHECK UP(定期维护保养)

注释:   为确保本产品之性能保持在最理想状态,定期检查及维护UPS 是必要的,假如UPS 出现A18: PERIODIC SERVICE CHECK UP 警讯时,即代表本UPS 需执行维护保养工作。需要工程师现场服务。